Veris H614
SKU: CS3098877MPN: H614Alternate Part #: VER-H614
Current Switch: VFD, Automatic Trip Point, 1.5-150 Amp Range, Normally Open 1.0A@30VAC/DC, +/-20% Nominal Trip Point Target Range, Split-Core Housing

$102.51
UnitAvailable on backorder
Product Details
Current Switch:
- VFD* Automatic Trip Point* 1.5-150 Amperage Range* Normally Open 1.0A@30VAC/DC* +/-20% Nominal Trip Point Target Range* Split-Core* Sensor Power: Induced from monitored conductor* Response Time: 1 sec.* Learn Time: 15 sec. learn period after frequency stabilizes* Frequency Range: 12 to 115 Hz* Temperature Range -15 deg. to 60 deg. C (5 deg. to 140 deg. F)* Humidity Range: 10-90% RH non-condensing* Alarm Limits: ±20% of learned current in every 5 Hz freq. band* NORMAL-to-ALARM Status Output Delay: 5 second max.* ALARM-to-NORMAL Status Output Delay: 1 sec. nominal* Off Delay: \< 30 sec. nominal* Contact Ratings: 30VAC/DC, 1A* Insulation Class: 600VAC (UL); 300VAC RMS (CE)* Terminal Block Maximum Wire Size: 14 AWG* Terminal Block Torque (nominal): 3.54 to 4.43 in-lbs (0.4 to 0.5 N-m)* Agency Approvals: UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2
Specifications
| SKU | CS3098877 |
|---|---|
| MPN | H614 |
| Alternate Part # | VER-H614 |