ACI BN2120-R2

SKU: CS6289618MPN: BN2120-R2Alternate Part #: 146604

BACnet MS/TP, Modbus RTU, Relative Humidity, Room (R2)

Contact us for pricing and availability

Product Details

BACnet MS/TP, Modbus RTU, Relative Humidity, Room (R2)

Product Configuration

Category Humidity

Product Family Specifications

Resolution +/- 0.1º | +/- 0.1%
Product Weight 0.21 lbs. (0.095 kg)
Supply Current 25 mA maximum (0.67 VA)
Supply Voltage 12 to 36 VDC | 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
Enclosure Color White
Agency Approvals BTL Certified, CE, RoHS, WEEE, China RoHS
Maximum Distance 4000 ft (1219 m)
Temperature Units ºF (Factory Default), ºC, ºK (Field Configurable)
Operating RH Range 10 to 95% RH, non-condensing
Output Update Rate 4 seconds
Product Dimensions 4.50” (114.3 mm) x 2.78” (70.6 mm) x 1.40” (35.6 mm)
Network Addressable 0 \= Factory Default | 1-127 \= Field Selectable
RH Measurement Range 0 to 100%
Supported Baud Rates Auto Baud (Factory Default) | 9600, 19200, 38400, 57600, 76800, 115200 (Field Selectable)
Tri-Color Status LED Connection Status
RH Calibration Offset +/- 10% RH (Field Configurable)
Communication Protocol BACnet™ MS/TP or Modbus RTU \= Field Selectable; EIA RS-485
Connections | Wire Size Screw Terminal Blocks | 16 AWG (1.31 mm2) to 22 AWG (0.33 mm2)
Accuracy @ 77°F (25°C) +/- 1.0ºF (+/- 0.5ºC)
Storage Temperature Range -40 to 185ºF (-40 to 85ºC)
Operating Temperature Range 35 to 122ºF (1.5 to 50ºC)
RH Accuracy @ 77°F (25°C) +/- 2% from 10 to 90% RH
Temperature Measurement Range 35 to 122ºF (1.5 to 50ºC)
Temperature Calibration Offset +/- 9ºF (+/- 5ºC) (Field Configurable)
End of Line Termination Resistance 120 Ohms Termination Resistance (Field Selectable)
Modbus Data Bits / Parity / Stop Bit 8 Data Bits | None/Even/Odd \= Field Selectable | 1 or 2\= Field Selectable
Enclosure Material | Flammability Rating ABS Plastic | UL94-HB

Specifications

SKUCS6289618
MPNBN2120-R2
Alternate Part #146604