ACI QTS-61211X-E000000
SKU: CS6287914MPN: QTS-61211X-E000000Alternate Part #: 137713
Toxic Gas Sensor, Hydrogen, 0-2000 PPM, 4-20mA Output loop powered, Industrial NEMA 4X, Aluminum Sensor Housing

Contact us for pricing and availability
Product Details
Toxic Gas Sensor, Hydrogen, 0-2000 PPM, 4-20mA Output loop powered, Industrial NEMA 4X, Aluminum Sensor Housing
Product Configuration
| Gas Type | Hydrogen |
|---|---|
| Enclosure | Hazardous (CL.I, Div 1\&2) |
Product Family Specifications
| Accuracy | +/- 2.5% of Reading |
|---|---|
| Sensor Life | 2 to 3 years, typical |
| Sensor Type | Electrochemical, non-consuming |
| Repeatability | +/- 1% of Reading |
| Response Time | T90: \< 60 Seconds, typical |
| Output Signals | 4-20 mA (2-Wire, Loop Powered) |
| Product Weight | Industrial “E”/“S” Enclosures: 5.00 lbs (2.27kg) Commercial “C”/“D”/“N” Enclosures: 2.00 lbs (0.91kg) |
| Unit Shelf Life | 6 Months from date of purchase (Must be installed and operational) |
| Agency Approvals | RoHS, CSA-4828-02 (CSA File #: 088890 0 000 for Industrial Enclosure Options Only) |
| Factory Set Range | See Gas Sensor Selection \& Specification Table on back of data sheet |
| Product Dimensions | Commercial “C” Enclosure: 6.60” (167.64 mm) x 4.23” (107.44 mm) x 2.60” (66.04 mm) Commercial “D”\& “N” Enclosure: 6.60” (167.64 mm) x 4.23” (107.44 mm) x 3.70” (93.98 mm) Industrial “E”\& “S” Enclosure: 10.70” (271.78 mm) x 5.71” (145.04 mm) x 4.25” (107.95 mm) |
| RFI/EMI Protection | 4.0 Watts @ 1m (3.28 ft) Radiated |
| Operating Environment | Indoor Use only |
| Connections | Wire Size | Screw Terminal Blocks, 16 to 24 AWG (0.51 to 1.30 mm) Shielded Twisted Pair |
| Maximum Load (@ 24 VDC) | 600 Ohms |
| Recommended Maintenance | Accuracy \& Bump test every 3 to 6 months or as required by Code | Replace sensor as need |
| Operating Humidity Range | 0 to 90% RH, non-condensing (Continuous); 0 to 95% RH, non-condensing (Intermittent) |
| Operating Temperature Range | See Gas Sensor Selection \& Specification Table on back of data sheet |
| Supply Voltage / Protection | +24 VDC nominal (+12 to 36 VDC Load Dependent) | 0.5A Socketed Pico Fuse |
| Terminal Block Torque Rating | 0.37 ft-lb (0.502 Nm) Nominal |
| Operating Atmospheric Pressure | 14.696 psi (1.0132 bar) +/- 10% Note: When installed @ > 3000’ above sea level, the gas transmitters must be veried for accuracy \& re-calibrated as needed after installation |
| Storage Temperature | RH Range | 32 to 68ºF (0 to 20ºC) | 15 to 90% RH, Non-Condensing |
| Coverage Area / Mounting Height | See Gas Sensor Selection \& Specification Table on back of data sheet |
| Supply Current / Power Consumption | 25 mA maximum | 0.9 Watts maximum |
| Intrinsic Safety Barrier Requirement | 28.5 VDC maximum and 300 minimum load Note: Requirements to meet when installed with CSA Approved Intrinsic Safety Barriers in Class A, B, C \& D Certified environments |
| Enclosure Specifications (Type, Material Type, Flammability, NEMA/IP Rating, Explosion Proof) | Commercial “C”: General Purpose (Wall Mount); ABS Plastic, UL94 V-0; NEMA 1 (IP10) Commercial “D”: General Purpose (Duct Mount); ABS Plastic, UL94 V-0; NEMA 1 (IP10) Commercial “N”: Weatherproof (Wall Mount); ABS Plastic; UL94 V-0; NEMA 4X (IP56) Industrial “E”: Industrial Connection Head; Aluminum (Epoxy Coated); NEMA 4X (IP56) and Enclosure meets Type 7 \& 9 Explosion Proof Class 1 Div. 1, Groups B, C, D also Group A; CSA, FM (Factory Mutual), EX (Explosion Proof), UL listed Industrial “S”: Industrial Connection Head; 316 Stainless Steel; NEMA 4X (IP56) and Enclosure meets Type 7 \& 9 Explosion Proof Class 1 Div. 1, Groups B, C, D also Group A; CSA, FM (Factory Mutual), EX (Explosion Proof), UL listed Note for E \& S enclosure: The Cl2, ClO2, HCl, SO2, NO2, NH3, and O3 sensor assemblies are NOT explosion-proof rated |
Specifications
| SKU | CS6287914 |
|---|---|
| MPN | QTS-61211X-E000000 |
| Alternate Part # | 137713 |