ACI RM2432DE
SKU: CS6287085MPN: RM2432DEAlternate Part #: 131063
Wireless, Sensor Receiver, 4 Analog (0 to 10 or 0-5VDC) \& 4 Digital Outputs, NEMA 4X Enclosure

Contact us for pricing and availability
Product Details
Wireless, Sensor Receiver, 4 Analog (0 to 10 or 0-5VDC) \& 4 Digital Outputs, NEMA 4X Enclosure
Product Configuration
| Enclosure | NEMA 4X |
|---|
Product Family Specifications
| Connections | 16 to 26 AWG shielded twisted pair |
|---|---|
| Data Protocol | IEEE 802.15.4-2003/2006 |
| Analog Outputs | Four (4) 0-5/10V jumper selectable |
| Product Weight | Standard: 2.00 lbs (0.91 kg) | NEMA 4X: 2.46 lbs (1.12 kg) |
| Supply Current | 300 mA |
| Supply Voltage | 24 VAC, 60 Hz (Full wave rectified) |
| Relay Durability | Mechanical: 5,000,000 operations minimum @ 36K operations/hr Electrical: 100,000 operations minimum (under rated load @ 1.8K operations/hr) |
| Lost Signal Alarm | (1) SPDT, Dry contact relay, 1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC) Resistive |
| Product Dimensions | Standard: (L) 8.78” (223.01 mm) x (W) 4.72” (119.89 mm) x (H) 2.36“ (59.94 mm) NEMA 4X: (L) 8.74” (222.00 mm) x (W) 5.74” (145.80 mm) x (H) 2.96” (75.18 mm) |
| RF Characteristics | 900 MHz, Operating Frequency 10 channels between 902 – 928 MHz Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm |
| Digital Output Type | Four (4) SPDT Pilot Duty Relays, Dry Contact |
| System Requirements | • Laptop with Windows 98, XP, Vista, Windows 7 or Windows 10, Ethernet Port, and 10 GB memory • Direct connection from PC to RM2402D using CK2432D serial to RJ11 Programming Cable • USB to Serial Adapter (Not provided by ACI) • IP Address of PC must have static address of 192.168.0.2 or above |
| Contact (Load) Rating | 1.0A, 30 VDC @ 104ºF (40ºC), 0.5A, 125 VAC @ 104ºF (40ºC) Resistive |
| Transmission Distance | 200 – 300 ft horizontally depending on building type and constructions, and typically one floor above and below the transceiver vertically |
| Configuration Software | Included; Data registers need to be configured prior to use |
| Operating Humidity Range | 30 to 50% RH, Noncondensing |
| Storage Temperature Range | -4 to 176ºF (-20 to 80ºC), 70% RH |
| Operating Temperature Range | 32 to 140ºF (0 to 60ºC) |
| Terminal Block Torque Rating | 0.37 ft-lb (0.5 Nm) Nominal |
| Enclosure Material | Flammability Rating | Standard: ABS Plastic | UL94-5VA | NEMA 4X: Polycarbonate Plastic | UL94 HB |
Specifications
| SKU | CS6287085 |
|---|---|
| MPN | RM2432DE |
| Alternate Part # | 131063 |