ACI F200
SKU: CS6290191MPN: F200Alternate Part #: 147702
Monitoring Appliance (Temp/RH/Leak), (8) DI, (4) RJ-11 Inputs, Relay Output, Alarm, Logging, Trending, Protocols: TCP/IP, HTML, SMTP, Modbus TCP/IP…

Contact us for pricing and availability
Product Details
Monitoring Appliance (Temp/RH/Leak), (8) DI, (4) RJ-11 Inputs, Relay Output, Alarm, Logging, Trending, Protocols: TCP/IP, HTML, SMTP, Modbus TCP/IP, SNMP
Product Configuration
| Enclosure | Metal |
|---|---|
| Controller Type | Zone |
| Temperature Series | None |
| Controller Maximum Sensing Cable | 200ft (61m) |
Product Family Specifications
| Relay Output | SPDT (Form C) Dry Contacts |
|---|---|
| Product Weight | 0.438 lbs (0.199 kg) |
| Supply Current | 0.1 Amp Maximum |
| Supply Voltage | 24 VAC or 24VDC (+/- 10%) Note: If a DC power supply is used, the A/SLD will be a latching device (once an alarm is detected, the spot detector will remain in an alarm state until power is cycled to the A/SLD) |
| Agency Approvals | CE; ETL listed: conforms to UL 61010-1, EN 61010-1; RoHS compliant |
| Operating Altitude | 15,000ft (4,752m) Maximum |
| Product Dimensions | 2.0”(50.8mm) x 1.55”(39.4mm) x 1.0”(25.4mm) |
| Relay Contact Rating | 1A @ 24VDC, 0.5A resistive @ 120VAC |
| Operating Humidity Range | 5% to 95% non-condensing |
| Storage Temperature Range | -4 to 158F (-20 to 70C) |
| Operating Temperature Range | 32 to 122F (0 to 50C) |
| Wire Lead Length (Non-sensing) | 14’ (4.27m) |
Specifications
| SKU | CS6290191 |
|---|---|
| MPN | F200 |
| Alternate Part # | 147702 |