// 500+ Brands

// Authorized Distributor of Over 100 Brands

Dwyer SL-2000-P

SKU: CS4112803MPN: SL-2000-PAlternate Part #: 128078-01

SL-2000-P DCT SMK DET PHOTOELE

$355.80
Unit
Available on backorder
remove
add

Product Details

Conventional, 4-wire, universal voltage, photoelectric duct smoke detector

Attributes

Air Velocity Range 100 to 4000 FPM.
Ambient Temperature SL-2000-N: 32°F to 158°F (0°C to 70°C); SL-2000-P: 32°F to 140°F (0°C to 60°C).
Commodity Code R3AE
Compliance cULus (UL 268A) File # S2829, CSFM Listed (3240-1004:105), MEA Accepted (73-92-E; VOL. 27).
Electrical Connection Screw terminals.
Electrical Rating Alarm contacts: 2 sets form x0080__x009c_C_x0080__x009d rated at 10 A resistive @ 115 VAC and 1 set form x0080__x009c_A_x0080__x009d rated at 2 A; Trouble contacts: 1 set form x0080__x009c_C_x0080__x009d rated at 10 A @ 115 VAC.
Enclosure Grey plastic back box, clear plastic cover (Makrolon 94V-0).
Enclosure Rating SL-2000: NEMA 1; WP-2000: NEMA 3R.
Humidity Limit 85 ±5 % RH (@32 ±2°C; 86 ±3.6°F) Non-condensing/Nonfreezing.
Power Requirement Standby: 230 VAC (12 mA), 115 VAC (22 mA), 24 VAC (55 mA), or 24 VDC (14 mA); Alarm: 230 VAC (18 mA), 115 VAC (32mA), 24 VAC (190 mA), or 24 VDC (68 mA).Standby: 230 VAC (12 mA), 115 VAC (22 mA), 24 VAC (55 mA), or 24 VDC (14 mA); Alarm: 230 VAC (18 mA), 115 VAC (32mA), 24 VAC (190 mA), or 24 VDC (68 mA).
Radioactive Element For SL-2000-N (Ionization) americium 241; 0.9 Micro-curie; Do not expose to corrosive atmospheres.
Sensor Type Photoelectric or Ionization.

Specifications

SKUCS4112803
MPNSL-2000-P
Alternate Part #128078-01