ACI ACUCT-H040-40:333
SKU: CS6290354MPN: ACUCT-H040-40:333Alternate Part #: 148161
Current Transformer, 40A, Hinged Split Core, 0.4” Aperture, 333mV Output, 2.5m Leads

Contact us for pricing and availability
Product Details
Current Transformer, 40A, Hinged Split Core, 0.4” Aperture, 333mV Output, 2.5m Leads
Product Configuration
| Amperage Range | 0 to 40 Amps |
|---|
Product Family Specifications
| Accuracy | 0.5% from 10-120% of Rated Current |
|---|---|
| Wire Size | 22 AWG (0.14 mm2), 600V Rated VW-1, 105°C Black/Brown Twisted Pair (UL 1015) |
| Core Style | Hinged Split-Core |
| Lead Length | 8.20’ (2.5m) or 32.80’ (10m) See Ordering Grid8.20’ (2.5m) or 32.80’ (10m) See Ordering Grid |
| Rated Output | 333mV @ 20/30/40/50/60/100/200 Amps (see ordering grid) |
| Product Weight | AcuCT-H040 Series: 0.2lbs (0.09kg) AcuCT-H100 Series: 0.4lbs (0.18kg) |
| Agency Approvals | ULR, CE, \& RoHS2 Compliant |
| Lead Wire Colors | White: Positive (+) Black: Negative (-) |
| Maximum Elevation | 9,842 ft (3 Kilometers) |
| Maximum AC Voltage | 600 VAC, Category III |
| Product Dimensions | AcuCT-H040 Series: 1.64” (41.66 mm) x 1.16” (29.47 mm) x 1.04” (26.42 mm) AcuCT-H100 Series: 2.76” (70.11 mm) x 2.00” (50.80 mm) x 1.52” (38.61 mm) |
| Wiring Connections | Stripped and Tinned Lead Wires |
| Monitored Current Type | AC Current |
| Operating Frequency Range | 50/60Hz |
| Storage Temperature Range | -40 to 185°F (-40 to 85°C) |
| Operating Temperature Range | 5 to 140°F (-15 to 60°C) |
| Operating/Storage Humidity Range | 5 to 95%, non-condensing |
| Enclosure Material | Flammability Rating | Black Nylon/UL94V-0 |
Specifications
| SKU | CS6290354 |
|---|---|
| MPN | ACUCT-H040-40:333 |
| Alternate Part # | 148161 |