SKU: CS6286806MPN: AFP VERSION #5Alternate Part #: 128283
Analog Input, Floating Point Output (90 sec), Version #5, (135, 180s Selectable), Relay stays on with 5% of Max/Min

Contact us for pricing and availability
Product Details
Analog Input, Floating Point Output (90 sec), Version #5, (135, 180s Selectable), Relay stays on with 5% of Max/Min
Product Configuration
| Output Rate Of Change | 90, 135, 180 Seconds |
|---|
Product Family Specifications
| Wire Size | 16 (1.31 mm2) to 26 AWG (0.129 mm2) |
|---|---|
| Connections | 90° Pluggable Screw Terminal Blocks |
| Product Weight | 0.325 lbs. (0.147 Kg) |
| Supply Current | 105 mA maximum without 24 VDC auxiliary output 190 mA maximum with 24 VDC auxiliary output |
| Supply Voltage | 24 VAC or 24 VDC, (+/- 10%), 50/60 Hz |
| Input Impedance | Voltage @ 10,000Ω Nominal / Current @ 250Ω nominal |
| Agency Approvals | RoHS2, WEEE |
| Operating RH Range | 10 to 95% non-condensing |
| Product Dimensions | (L) 4.00” (W) 3.25” (H) 1.15” (101.6 x 82.55 x 29.21 mm) |
| Snaptrack Material | UL94 V-0 |
| Relay Contact Rating | Dry Contact, Form C, 2A maximum @ 24 VDC |
| Relay Electrical Life | 100,000 operations minimum |
| Relay Mechanical Life | 1,000,000 operation |
| Output (Floating Point) | Two relay contact outputs (Increase / Decrease) |
| Storage Temperature Range | -20 to 150°F (-28.9 to 65.5°C) |
| Operating Temperature Range | 35 to 120°F (1.7 to 48.9°C) |
| Terminal Block Torque Rating | 0.5 Nm (Minimum); 0.6 Nm (Maximum) |
| Input Current Signal Range (@ Impedance) | 0-20 mA |
| Input Voltage Signal Range (@ Impedance) | 0-5 VDC, 0-10 VDC, 0-15 VDC |
| Analog Current Signal Input Range with Offset Jumper | 4-20 mA |
| Analog Voltage Signal Input Range with Offset Jumper | 1-5 VDC, 2-10 VDC, 3-15 VDC |
Specifications
| SKU | CS6286806 |
|---|---|
| MPN | AFP VERSION #5 |