// 500+ Brands

// Authorized Distributor of Over 100 Brands

Dwyer DHII-007

SKU: CS3170438MPN: DHII-007Alternate Part #: 102127-06

DHII-007 0-10” WC

$1,119.58
Unit
Available on backorder
remove
add

Product Details

Differential pressure controller, selectable engineering units: 10.00” w.c., .8333 ft w.c., 254.0 mm w.c., 25.40 cm w.c., .3613 psi, .7356” Hg, 18.68 mm Hg, 24.91 mbar, 2491 Pa, 2.491 kPa, 24.91 hPa, 5.780 oz/in².

Attributes

Accuracy ±0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warmup).
Commodity Code 1902
Compensated Temperature Limits 32 to 140°F (0 to 60°C).
Compliance CE, UL.
Display 4 digit backlit LCD 0.6” height. LED indicators for set point and alarm status.
Electrical Connection Euro type removable terminal blocks with watertight conduit fittings for ½” watertight conduit.
Electrical Rating 8 amps at 240 VAC resistive.
Enclosure Rating Designed to meet NEMA 4 (IP66).
Housing Material Aluminum, glass.
Mounting Orientation Mount unit in horizontal plane.
Output Signal 4-20 mA DC into 900 Ω max.
Power Consumption Low voltage power = 24 VDC - 130 mA max; High voltage power = 100 to 240 VAC, 132 to 240 VDC - 7 VA max.
Power Requirement High voltage power = 100 to 240 VAC, 50 to 400 Hz or 132 to 240 VDC; Low voltage power = 24 VDC ±20%.
Pressure Limit Ranges x0089¤ 2.5 in w.c. = 2 psi; 5”: 5 psi; 10”: 5 psi; 25”: 5 psi; 50”: 5 psi, 100”: 9 psi.
Process Connection ⅛” female NPT.
Response Time 250 ms (dampening set to 1).
Serial Communication Modbus® RTU, RS485, 9600 Baud.
Service Air and non-combustible, compatible gases.
Set Point Adjustment Adjustable via keypad on face.
Stability < ±1% per year.
Switch Type 2 SPDT relays.
Thermal Effect 0.020%/°F (0.036/°C) from 77°F (25°C).
Wetted Material Consult factory.
Zero Span Adjustments Accessible via menus.

Specifications

SKUCS3170438
MPNDHII-007
Alternate Part #102127-06