ACI TUCH2-10F3-1EC0CX210N4C0-XX

SKU: CS6290303MPN: TUCH2-10F3-1EC0CX210N4C0-XXAlternate Part #: 148030

Microprocessor Based Sensor (RH \& Temp) LCD, RH2%:0-10V, 0-10 VDC, Deg F, Setpoint, Override

Contact us for pricing and availability

Product Details

Microprocessor Based Sensor (RH \& Temp) LCD, RH2%:0-10V, 0-10 VDC, Deg F, Setpoint, Override

Product Configuration

Configuration Room w/ Setpoint \& Override
Setpoint Options 0-10VDC
Accuracy (Humidity) +/-2%

Product Family Specifications

Product Weight 0.35 lbs (0.162 kg)
Supply Current Maximum: Current Outputs: 100 mA maximum; Voltage Outputs: 16 mA maximum
Supply Voltage 20-28 VAC / +12-40 VDC (Resistive Temp, 0-1V, 0-5V, 1-5 VDC Output Signals) 20-28 VAC / +18-40 VDC (Resistive Temp, 0-10V, 2-10V, 0-20 mA, and 4-20 mA Output Signals)
Override Option Normally-Open (N/O) Dry Contact Closure (See Ordering Grid for other Options)
Agency Approvals CE (EMC 2014/30/EU); RoHS
Operating RH Range 5 to 90% RH, non-condensing
Product Dimensions 4.56” (11.59 cm) x 3.00” (7.62 cm) x 1.26” (3.20 cm) (H x W x D)
Communication Jacks Option: RJ4 (4 Pin 4 Cond (RJ9, RJ10, RJ22 Phone)), RJ6 (6 Pin 6 Cond (RJ12 Phone)) and RS232 (⅛” (3.5 mm) Stereo Jack) 26 AWG Flying Leads with Wire Nuts
RH Measurement Range 0 to 100% RH
Display Numeral Height 0.600” (15.24 mm) (Large); 0.280” (7.11 mm) (Small)
LCD Display Descriptors ºF, ºC, % RH, Occupied / Unoccupied (Override Feedback), Set Point
Override Feedback Signal Dry Contact (Logic Low) or 5-30 VDC / 24 VAC (Logic High) (Specify when Ordering)
Storage Temperature Range -4 to 158ºF (-20 to 70ºC)
Enclosure Material | Color ABS/Polycarbonate Blend | White
Operating Temperature Range 40 to 104ºF (4.5 to 40ºC)
Terminal Block Torque Rating 4.4 lb-in (0.5 Nm)
Enclosure Flammability Rating UL 94-5VB
Temperature Measurement Range 40 to 100ºF, 40 to 90ºF, 50 to 90ºF, 50 to 100ºF, 55 to 85ºF (Others available) 4.5 to 40ºC, 4.5 to 32ºC, 10 to 32ºC, 10 to 35ºC, 13 to 32ºC (Others available)
Wiring Connections / Wire Size 12 Position Screw Terminal Blocks / Accepts 28 to 14 AWG (0.08 to 2.5 mm2)
Display Mean Time Between Failure (MTBF) 100,000 Hours Typical (When LCD Backlight set to ALWAYS ON)
Set Point Midpoint (Room Temp/RH Set Point) Select single point Temp from 55 to 89ºF (14 to 31ºC) and/or RH from 33 to 67%
LCD Backlight Color | LCD Backlight Function Blue | Turns on w/ Button Press (Default); Field adjustable (ALWAYS ON or OFF)
Override Contact Resistance | Life Expectancy \< 30 Ohms | 500,000 Actuations minimum
Set Point Differential (Scale Above/Below Midpoint) Select single point from +/- 1 to +/- 20º and/or +/- 1 to +/- 20% RH

Specifications

SKUCS6290303
MPNTUCH2-10F3-1EC0CX210N4C0-XX
Alternate Part #148030