SKU: CS6287744MPN: A/RH2-1K-NI-O-SUNAlternate Part #: 136846
Relative Humidity, RH Outputs: 0-5, 0-10 VDC \& 4-20mA (Default), Outside Air, ± 2% Accuracy, 1,000 Ohm Nickel RTD, Sun Shield

Contact us for pricing and availability
Product Details
Relative Humidity, RH Outputs: 0-5, 0-10 VDC \& 4-20mA (Default), Outside Air, ± 2% Accuracy, 1,000 Ohm Nickel RTD, Sun Shield
Product Configuration
| Accuracy (Humidity) | +/-2% |
|---|
Product Family Specifications
| Wire Size | 16 (1.31 mm²) to 26 AWG (0.129 mm²) |
|---|---|
| Connections | Screw Terminal Blocks (Polarity Sensitive) |
| Product Weight | 5.49 lbs. (2.49 kg) |
| RH Sensor Type | Capacitive with Hydrophobic Filter |
| Supply Current | Voltage Output: 8 mA maximum (0.32 VA) Current Output: 24 mA maximum (0.83 VA) |
| Supply Voltage | 4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC | 500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC Note: Reverse Polarity Protected |
| Agency Approvals | CE, RoHS, WEEE |
| RH Output Signal | 2-wire: 4 - 20 mA (Factory Default) 3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable) |
| Operating RH Range | 0 to 95% RH, non-condensing (Conformally Coated PCB’s) |
| Insulation | Rating | Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E |
| RH NIST Test Points | Default Test Points: 3 Points (20%, 50% \& 80%) 1% NIST Test Points: 5 Points within selected 20% Range (ie. 30%-50% are 30, 35, 40, 45 \& 50) |
| Nickel RTD Stability | +/-0.05% after 1000 Hours @ 302°F (150°C) |
| RH Measurement Range | 0-100% |
| RH Response Time (T63) | 20 Seconds Typical |
| Nickel RTD Din Standard | Din 43760 |
| Temperature Coefficient | 6370 ppm/°C |
| RH Output Load Resistance | 4-20 mA: 700 Ohms maximum 0-5 VDC or 0-10 VDC: 4K Ohms Minimum |
| Storage Temperature Range | -40 to 149°F (-40 to 65°C) |
| Nickel RTD Sensor Accuracy | 32°F (0°C): +/-0.72°F (0.4°F); 70°F (21.1°C): +/-0.34°F (0.17°C); 130°F (54.4°C): +/-1.00°F (0.56°C) |
| Operating Temperature Range | -40 to 140°F (-40 to 60°C) |
| RH Accuracy @ 77°F (25°C) | Model Dependent: +/- 1% over 20% RH Range between 20 to 90% | +/- 2%, or 3% from 10 to 95% |
| Lead Length | Conductor Size | 14” (35.6 cm) | 22 AWG (0.65 mm) |
| Terminal Block Torque Rating | 4.43 to 5.31 lb-in (0.5 to 0.6 Nm) |
| RH Transmitter Stabilization Time | 30 Minutes (Recommended time before doing accuracy verification) |
| RH Stability | Repeatability | Sensitivity | Less than 2% drift / 5 years | 0.5% RH | 0.1% RH |
| Sensing Tube Dimensions (Length x Diameter) | 6.83” (173.48 mm) x 0.740” (18.80mm) |
| Nickel RTD (PTC) Output @70°F (21.1°C) (Wire Colors) | 1000 Ohms nominal (1K-Nickel RTD) | Red/Red |
| Enclosure Specifications (Material, Flammability, Temperature, NEMA/IP Rating) | “-4X” Enclosure: Polystyrene Plastic; UL94-V2; -40 to 158°F (-40 to 70°C); NEMA 4X (IP 66) |
Specifications
| SKU | CS6287744 |
|---|---|
| MPN | A/RH2-1K-NI-O-SUN |
| Alternate Part # | 136846 |