Eaton PXM4251A1AB
SKU: CS4974868MPN: PXM4251A1ABUPC/EAN: 786685424835
Eaton Power Xpert meter 4000

Contact us for pricing and availability
Product Details
Power Xpert Meter 4000, Standard power quality, 2 GB, Voltage input; Standard plus auxiliary (V6, V7, V8), Standard 100-240 Vac or 110-250 Vdc power supply, I/O option card (8 digital inputs, 2 solid state outputs, 3 relay outputs)
Attributes
| Thd Current And Voltage | To 127th |
| Ansi Revenue Accuracy | C12.20 (0.2) |
| Communications | 1xRS-485 1 x Local Ethernet Port for configuration Fiber-optic Ethernet Port Internet/HTTP Server built-in 10/100 RJ-45 Ethernet Port BACnet/IP Network Time Protocol (NTP) Email (SMTP) Modbus RTU (RS-485) :2nd Simple Network Management Protocol (SNMP) Modbus TCP File Transfer Protocol (FTP) built-in |
| Current Sensor Input | 5A |
| I O Capability | Prog. Pulse Output –Wh, Varh, Vah Programmable Discrete Inputs - 8 Synchronize Demand Window Pulse Input Voltage Disturbance Trip Load Shedding KYZ output Programmable Relay Outputs -5 |
| Individual Harmonics Magnitude | To 85th |
| Instrumentation | Vars Ground Current Wh –Net Current & Voltage - Per Phase View current & voltage phasors on display Wh –Positive & Negative Watt Demand Neutral Current Current Demand Time Of Use Energy Demand Metering Current & Voltage - 3 Phase Average Current & Voltage - 3 Phase Min, Max Watts Vah Va Varh 4 Quadrant Energy Per Phase Power Factor Frequency Displacement Power Factor Current & Voltage - % Phase Unbalance - EVENT SETTING ONLY Voltage Neutral-Ground Va demand Apparent Power Factor |
| Logging | Time / date stamp Min/Max Log Event Log Data Logging Audible Alarm LED alarm indicator |
| Memory | 2 GB |
| Modification 1 | Standard communications module with RS-485 |
| Modification 3 | I/O option card (8 digital inputs, 2 solid state outputs, 3 relay outputs) |
| Power Quality Analysis | Number Of 9’S Availability View Harmonic Spectrum At Device Crest Factor K-Factor PQ Index Graph -STD |
| Power Supply Voltage | 100-240 V, 110-250 Vdc |
| Type | Standard power quality |
| Waveform Analysis | Captured Waveforms Displayed on Meter/GUI Comtrade - Standard IEEE File Format Voltage Disturbance Wave Capture Trigger Waveform recording duration - 60 cycles Waveform Captured On Threshold / Input Excess Dv/Dt Or Interruption Capture Trigger |
| Waveform Capture Sampling Rate | 4096 Oversampling/cycle |
Specifications
| SKU | CS4974868 |
|---|---|
| MPN | PXM4251A1AB |
| UPC/EAN | 786685424835 |