Dwyer 616KD-B-03-V
SKU: CS4124840MPN: 616KD-B-03-VAlternate Part #: 101693-50
616KD-B-03-V 0-5”WC VOLTAGE DP

$138.85
UnitAvailable on backorder
Product Details
Differential pressure transmitter, 0-5” w.c., +/- 1.0% FS, voltage
Attributes
| Accuracy | 616KD-A: ±0.25% FS; 616KD-B: ±1% FS, 616KD: ±2% FS. |
| Agency Approval | CE, UL Standard 2043. |
| Commodity Code | 0159 |
| Compensated Temperature Range | 20 to 122°F (-6.67 to 50°C). |
| Current Consumption | 24 mA max for 616KD A and B. 21 mA max for 616KD. |
| Electrical Connection | Screw-type terminal block. |
| Enclosure Rating | NEMA 1 (IP20). |
| Loop Resistance | 4 to 20 mA output (DC): 0 to 1250 Ω max. Rmax = 50(VpsDC -10) Ω; 4 to 20 mA output (AC): 0 to 1200 Ω max. Rmax = 50(1.4 VpsAC -12) Ω; Voltage output: 5 KΩ minimum. |
| Mounting Orientation | Vertical with pressure connections pointing down. |
| Output Signal | 4 to 20 mA or option with field selectable 0 to 10, 0 to 5, 2 to 10, 1 to 5 V. |
| Power Requirement | 4-20 mA output: 10 - 35 VDC (2 wire) or 12-26 VAC (4 wire); 5V output: 10 - 35 VDC (3 wire) or 12-26 VAC (4 wire); 10V output: 13 - 35 VDC (3 wire) or 12-26 VAC (4 wire) for 616KD A and B. 16 to 36 VDC (2 or 3 wire): 20 to 28 VAC (3 wire) for 616KD. |
| Pressure Limit | 2 psig (ranges 5” w.c. or lower); 5 psig (ranges 10 to 40” w.c.). |
| Process Connection | Barbed, dual size to fit ⅛” & 3/16” (3 mm and 5 mm) ID rubber or vinyl tubing. |
| Service | Air and non-combustible, compatible gases. |
| Stability | ±1% FS/year. |
| Thermal Effect | 616KD-A: ±0.02% FS/°F; 616KD-B: ±0.04% FS/°F; 616KD: ±0.06% FS/°F, includes zero and span. |
| Wetted Material | Consult factory. |
| Zero And Span Adjustment | Push button. |
Specifications
| SKU | CS4124840 |
|---|---|
| MPN | 616KD-B-03-V |
| Alternate Part # | 101693-50 |