Siemens BTE-050X4-F012
EBYPS FD 50HP 480V;2CONT SS TYPE1

Product Details
Note: Image may not represent actual item.
480 VAC, 50 HP NEMA 1 VFD with electronic 2 contactor bypass, graphical interface, and fused disconnect Siemens BT300 variable frequency drives are specifically designed for the demands of today’s HVAC systems. The BT300 drives are easy to use, easy to understand and easy to program. The increased focus on energy efficiency of variable flow systems has increased the need for easy-to-use and highly reliable variable frequency drives that reduce the cost of installation and maintenance while maximizing energy savings. Siemens BT300 Variable Frequency Drives are offered with conventional or electronic bypass options. Electronic Bypass The electronic bypass utilizes internal control boards that act as the brains and eliminate the control wiring, relay logic, and terminal blocks. They are replaced with advanced built-in features that are accessible from an electronic keypad.
Features:
- Advanced Keypad with Start-Up Wizards and Displays
- Full Bypass Control - even if the Bypass Board Fails
- Auto Bypass
- Pass Through I/O
- Additional HVAC I/O Capability
- Essential Service
Attributes
| Analog input, signal | Selectable voltage or current; resolution 0.1%; accuracy ± 1%; DC 0…10 V;DC 4…20 mA |
| Analog inputs, number | 2 |
| Analog output, signal | Selectable voltage or current; resolution 0.1%; accuracy ± 1%; DC 0…10 V;DC 0…20 mA |
| Analog outputs, number | 1 |
| Degree of protection | NEMA Type 1 |
| Digital input, signal | 0 to 5V = “0”; 15 to 30V = “1” |
| Digital inputs, number | 6 |
| Output current | 72 A |
| Output frequency | 0 to 320 Hz |
| Power output | 50hp, 37 kW |
| Relay outputs | 2 Form C, 1 Normally Open |
| Relay outputs, number | 2 |
| Relay output, switching voltage | 24 Vdc / 8A; 250 Vac / 8A; 125 Vdc / 0.4A |
| Communication | RS485 and Ethernet; Modbus RTU, Modbus TCP; BACnet MSTP, BACnet IP; Metasys N2 |
| Operating voltage | 480 VAC |
| Overload capacity | 1.1 × Nominal rated output current 110% for 1 minute/10 minutes |
| Protection functions | - Over-voltage and under-voltage trip limit - Ground fault protection - Mains supervision - Motor phase supervision - Over-current protection - Unit over-temperature protection - Motor overload and underload protection - Motor stall protection - Short-circuit protection of +24V and +10V reference voltages |
| Operating Temperature | 14° F (-10°C) (no frost) to 104°F (40°C); up to 122°F (50°C) with de-rating; 0 to 95% RH, non-condensing, non-corrosive |
| Housing | UL Type 1 |
| Product conformity | UL;cUL;CE |
| Frame Size | 7 |
| Frequency | 50/60 Hz |
Specifications
| SKU | CS3748576 |
|---|---|
| MPN | BTE-050X4-F012 |