// 500+ Brands

// Authorized Distributor of Over 100 Brands

Dwyer CMT200

SKU: CS3742037MPN: CMT200Alternate Part #: 101796-00

CMT200 200 PPM CO XMTR

$180.83
Unit
Available on backorder
remove
add

Product Details

Carbon Monoxide Transmitter, 0 to 200 PPM CO, 4 to 20 mA/2 to 10 VDC outputs.

Attributes

Accuracy ±2% FS at the time of calibration.
Calibration 15 turn span and zero adjustment potentiometers.
Commodity Code 0606
Compliance CE.
Coverage Area 5000 to 7000 sq. ft. typical.
Electrical Connection Removable terminal block, includes two PG11 and one PG 16 knockouts for conduit fitting.
Housing UV resistant polycarbonate.
Humidity Limit 15 to 90% RH constant; 0 to 99% RH intermittent.
Output Jumper selectable 4 to 20 mA (loop powered) or 2 to 10 V (load must be >50 kΩ).
Output Drift <5% per year in air.
Power Requirement Current Output: 18 to 28 VDC; Voltage Output: 18 to 28 VDC/VAC, reverse polarity protected.
Range 0 to 200 ppm.
Response Time <45 s. to 90% of final value.
Sensor Field replaceable electrochemical, 4 year typical lifespan.
Storage Temperature For best sensor life, 32 to 68°F (0 to 20°C).

Specifications

SKUCS3742037
MPNCMT200
Alternate Part #101796-00