Belimo PRXUP-MFT-T-250

SKU: CS3357197MPN: PRXUP-MFT-T-250

Configurable Valve Actuator, Non fail-safe, AC 24...240 V / DC 24...125 V, 2...10 V, 2 x SPDT, terminals, BACnet MS/TP Modbus RTU MP-Bus, MFT/progr…

$3,258.67
Unit
Available on backorder
remove
add

Product Details

Configurable Valve Actuator, Non fail-safe, AC 24...240 V / DC 24...125 V, 2...10 V, 2 x SPDT, terminals, BACnet MS/TP Modbus RTU MP-Bus, MFT/programmable

Attributes

Control MFT/programmable
Auxillary Switch 2 x SPDT
Fail-Safe Non-Spring Return
Nominal Voltage AC 24…240 V / DC 24…125 V
Transformer Sizing 20 VA @ AC/DC 24 V (class 2 power source), 23 VA @ AC/DC 120 V, 52 VA @ AC 230 V
Enclosure UL Enclosure Type 4X
Power Supply 24…240 VAC, -20% / +10%, 50/60 Hz, 24…125 VDC, -20% / +10%
Power Consumption In Operation 20 W
Power Consumption In Rest Position 6 W
Electrical Connection Terminal blocks, (PE) Ground-Screw
Overload Protection electronic thoughout 0…90° rotation
Operating Range 2…10 V (default), 4…20 mA, variable (VDC, on/off, floating point)
Operating Range Y Variable Start point 0.5…30 V End point 2.5…32 V
Input Impedance 100 kΩ for 2…10 V (0.1 mA), 500 Ω for 4…20 mA, 1500 Ω for On/Off
Position Feedback 2…10 V, Max. 0.5 mA, VDC variable
Angle Of Rotation 90°
Direction Of Motion Motor reversible with app
Position Indication integral pointer
Running Time (Motor) default 35 s, variable 30…120 s
Ambient Humidity max. 95% r.H., non-condensing
Ambient Temperature -22…122°F [-30…50°C]
Storage Temperature -40…176°F [-40…80°C]
Degree Of Protection Iec/En IP66/67
Degree Of Protection Nema/Ul NEMA 4X
Connection terminals
Servicing maintenance-free
Housing Material Die cast aluminium and plastic casing
Nominal Voltage Dc 24…125 V
Nominal Voltage Ac 24…240 V
Noise Level, Motor 68 dB(A)
Quality Standard ISO 9001
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU
Auxiliary Switch 2 x SPDT, 3 A resistive (0.5 A inductive) @ AC 250 V, 1 x 10° / 1 x 0…90° (default setting 85°)
Fail-Safe Function Non fail-safe
Control Type Web MFT/Programmable
Fail-Safe NO

Specifications

SKUCS3357197
MPNPRXUP-MFT-T-250