ACI FS-2
SKU: CS3149351MPN: FS-2Alternate Part #: 102484
Freeze Stat, 20’ Capillary, Manual Reset, (2) SPDT

Contact us for pricing and availability
Product Details
Freeze Stat, 20’ Capillary, Manual Reset, (2) SPDT
Product Configuration
| Length | 20’ |
|---|---|
| Reset Style | Manual |
| Number Of Relays | 2 |
Product Family Specifications
| # of Relays | Model Dependent: 1 or 2 |
|---|---|
| Cable Entry | One (1) M20 compression fitting, removable, hole fits ½ in. conduit connector |
| Contact Form | Form 1C (SPDT Contact) |
| Reset Options | Model Dependent: Manual or Automatic |
| Sensing Media | Temperature in air |
| Product Weight | 1.6 lbs (0.7 kg) |
| Enclosure Color | Silver / Light Gray |
| Sensing Element | Vapor-filled capillary |
| Thermostat Type | Self-contained, electromechanical |
| Type of Control | ON/OFF, low-level single-stage or cut-out control, with One (1) microswitch output |
| Agency Approvals | CE |
| Enclosure Rating | NEMA 1 (IP40) |
| Sensing Response | To lowest temperature sensed by any 1 ft section of the capillary element |
| Maximum Wire Size | 14 AWG (2.5 mm²) |
| Wiring Connections | Terminal with wire-retaining screws |
| Switching Differential | 1.8°F (1°K), auto- or manual reset |
| Enclosure Base Material | Steel, galvanized |
| Enclosure Cover Material | ABS, fire retardant |
| Operating Humidity Range | 0 to 95% RH, non-condensing |
| Sensing Capillary Length | Model Dependent: 6’ (1.8m), 10’ (3m), 20’ (6m), 50’ (16m) |
| Storage Temperature Range | 14°F to 158°F (-10°C to 70°C) |
| Sensing Capillary Diameter | Ø0.08 in. (2 mm) (6’ Length models have a larger bulb at the end) |
| Sensing Capillary Material | Copper |
| Adjustable Trip Point Range | 14°F to 54°F (-10°C to 12°C) |
| Low-Level Setpoint Adjustment | Over full operating range, via screwdriver slot |
| Sensing Capillary Installation | Duct and across coil mounted |
| Low-Level Setpoint Visual Range | 14°F to 54°F |
| Enclosure Dimensions (L x W x H) | 4.1” (105 mm) x 3.3” (83 mm) x 2.1” (53 mm) |
| Low-Level Setpoint (Factory Set) | At 39°F (4°C), and safety-lock secured |
| Maximum Contact Switching Current | 15 (8) A |
| Maximum Contact Switching Voltage | 250 VAC |
| Enclosure Operating Temperature Range | 14°F to 131°F (-10°C to 55°C) |
| Sensing Capillary Overload Temperature | 392°F (200°C), maximum 60 minutes |
Specifications
| SKU | CS3149351 |
|---|---|
| MPN | FS-2 |
| Alternate Part # | 102484 |