// 500+ Brands

// Authorized Distributor of Over 100 Brands

ACI A/100-LTS-6'

SKU: CS2712673MPN: A/100-LTS-6'Alternate Part #: 125171

100 Ohm (Three Wires) RTD, 2” Freezer Probe 316 SS, 6’

Contact us for pricing and availability

Product Details

100 Ohm (Three Wires) RTD, 2” Freezer Probe 316 SS, 6’

Product Configuration

NIST None
Wire 6’ Teflon Insulated, LTS Only
Sensor 100-LTS (100 Ω, Freezer)
Enclosure None

Product Family Specifications

NEMA Rating “-GD” Enclosure: NEMA 1 (IP10) | “-4X” Enclosure: NEMA 4X (IP 66)
Number Wires Three Conductors (White and Two Red Wires); Polarity Sensitive (Tie Red wires together)
Product Weight A/xx-LTS-10’: 0.16lbs (0.073kg) | A/xx-LTS-4X-10’: 0.40lbs (0.181kg) A/xx-LTS-GD-10’: 0.71lbs (0.322kg) | A/xx-LTS-30’: 0.36lbs (0.163kg) A/xx-LTS-4X-30’: 0.60lbs (0.272kg) | A/xx-LTS-GD-30’: 0.91lbs (0.413kg)
Agency Approvals CE, UKCA, WEEE, RoHS
Number Sensing Points One
Operating Humidity Range 10 to 100% RH
Storage Temperature Range -40 to 80ºC (-40 to 176ºF)
Sensor Type | Sensor Curve Platinum RTD | Linear, PTC (Positive Temperature Coefficient)
Enclosure Temperature Rating “-GD” Enclosure: -40 to 100ºC (-40 to 212ºF) “-4X” Enclosure: -40 to 70ºC (-40 to 158ºF)
Lead Length | Conductor Size 10’ (3.05 m) or 30’ (9.15 m) | 0.106” nominal (2.69 mm)
Platinum RTD Tolerance Class Class B Accuracy Formula: +/- ºC \= (+/- 0.30ºC + (0.005 x |t|)) where t is the Absolute Value of temperature in ºC above or below 0ºC -200ºC (-328ºF): +/- 1.30ºC (+/- 2.34ºF) | 0ºC (-32ºF): +/- 0.30ºC (+/- 0.54ºF)
Sensor Output @ 0ºC (32ºF) A/100-LTS Series: 100 Ohms nominal | A/1K-LTS Series: 1000 Ohms nominal
Probe Material | Length | Diameter 316 Stainless Steel | 2” (50.8 mm) | 0.1875” (4.76 mm) nominal
Sensor Operating Temperature Range -198 to 150ºC (-324 to 302ºF)
Conductor Size | Conductor Material 24 AWG (0.51 mm) | Silver Plated Copper
Lead Wire Insulation | Jacket Color FEP/FEP (Teflon) Jacketed Cable | White
Cable Gland IP Rating | Torque Rating 2.5 Nm (22.127 lb. inch)
Din Standard | Temperature Coeffcient 3850 ppm / ºC | DIN EN 60751 (IEC 751)
Enclosure Material | Flammability Rating “-GD” Enclosure: Galvanized Steel | “-4X” Enclosure: Polystyrene | UL94-V2
Platinum RTD Response Time (63% Step Change) A/100-LTS Series: In still air: 3:40 (Min:Sec) In water: 19 (Sec) A/1K-LTS Series: In still air: 3:50 (Min:Sec) In water: 22 (Sec)
Cable Gland Sleeve Material | Wire Clamping Size Polyamide 6 | Neoprene 0.098” (2.5 mm) to 0.256” (6.5 mm) | IP 68 (NEMA 6P)
Cable Gland (Fitting) Size | Hole Size | Material PG7 | 15 mm (0.591”)

Specifications

SKUCS2712673
MPNA/100-LTS-6'
Alternate Part #125171