Square D GVAX116
SKU: CS1658895MPN: GVAX116
Undervoltage release (MN), TeSys Deca, 110-115 V AC 60 Hz, safety device for use with GV2ME
Contact us for pricing and availability
Product Details
TeSys GV electrical trip, MN undervoltage release, 110-115V AC 60Hz, for motor circuit breakers GV2ME used in safety-related systems. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, INRS, VDE 0113), Green Premium compliant (RoHS/REACh).
Specifications
| SKU | CS1658895 |
|---|---|
| MPN | GVAX116 |